miniature circuit-breakers DLS 6hdc B50-1


Details
Circuit-breakers, one-pole, B-characteristic, 50 A@125 V (DC), 6 kA, for DC circuits
Miniature circuit-breakers protect cables, conductors, and installation devices against overload and short circuit. Each of our circuit-breakers is equipped with a trip-free mechanism that ensures safe disconnection – even if the toggle is mechanically blocked. Our DLS 6hdc MCBs are designed for distribution and final circuits in direct current networks. Their rated breaking capacity is 6 kA. With tripping characteristic B, these circuit-breakers ensure reliable protection for your circuits without high inrush currents.
For use in DC networks, Rated switching capacity 6 kA, Strain-relief clamps with wide clamp cross section area for rail and cable wiring on both connector sides , special quick fastening for removal of multiple miniature circuit-breakers from the bottom or top interconnection, large, folding label window for a secure hold and protection of the label, use of conventional wiring rails, ON/OFF switch position indicator on the switch toggle, accessories retro-fittable on the right, labelling software free of charge
quick fastening to mounting rail, any installation position
Suitable for use in DC power supplies for residential and purpose-built buildings or buildings for commercial use.
Bearing of the ambient temperature on thermal tripping: lowering of the current values for higher ambient temperature and increasing for lower temperatures by about 5% for every 10°C temperature difference, For 2-pole devices, note that the poles must be connected in series.
- Mounting instruction
- Data sheet
- Prospectus DLS 6 IEC
- Manual Miniature circuit-breakers - Application notes and technical information
- Text for invitation to tender RTF
- Text for invitation to tender GAEB XML
- Text for invitation to tender GAEB 2000
- Text for invitation to tender GAEB 90
- Dimensional drawing Group view
- STEP file
- Wiring diagram
Circuit-breakers, one-pole, B-characteristic, 50 A@125 V (DC), 6 kA, for DC circuits
Miniature circuit-breakers protect cables, conductors, and installation devices against overload and short circuit. Each of our circuit-breakers is equipped with a trip-free mechanism that ensures safe disconnection – even if the toggle is mechanically blocked. Our DLS 6hdc MCBs are designed for distribution and final circuits in direct current networks. Their rated breaking capacity is 6 kA. With tripping characteristic B, these circuit-breakers ensure reliable protection for your circuits without high inrush currents.
For use in DC networks, Rated switching capacity 6 kA, Strain-relief clamps with wide clamp cross section area for rail and cable wiring on both connector sides , special quick fastening for removal of multiple miniature circuit-breakers from the bottom or top interconnection, large, folding label window for a secure hold and protection of the label, use of conventional wiring rails, ON/OFF switch position indicator on the switch toggle, accessories retro-fittable on the right, labelling software free of charge
quick fastening to mounting rail, any installation position
Suitable for use in DC power supplies for residential and purpose-built buildings or buildings for commercial use.
Bearing of the ambient temperature on thermal tripping: lowering of the current values for higher ambient temperature and increasing for lower temperatures by about 5% for every 10°C temperature difference, For 2-pole devices, note that the poles must be connected in series.
- Mounting instruction
- Data sheet
- Prospectus DLS 6 IEC
- Manual Miniature circuit-breakers - Application notes and technical information
- Text for invitation to tender RTF
- Text for invitation to tender GAEB XML
- Text for invitation to tender GAEB 2000
- Text for invitation to tender GAEB 90
- Dimensional drawing Group view
- STEP file
- Wiring diagram