residual current circuit-breaker DFS 4 100-4/0,10-A S

09165905, Residual current circuit-breakers, four-pole, 100 A, 0,1 A, Type A, selective, N left
  • sensitive to pulsating and alternating currents, mains-voltage-independent
  • selective for the establishment of stacked applications
  • minimal power dissipation at each pole
  • large connection terminals up to 50 mm²

residual current circuit-breaker DFS 4 100-4/0,10-A S

09165905, Residual current circuit-breakers, four-pole, 100 A, 0,1 A, Type A, selective, N left
  • sensitive to pulsating and alternating currents, mains-voltage-independent
  • selective for the establishment of stacked applications
  • minimal power dissipation at each pole
  • large connection terminals up to 50 mm²

Details

Residual current circuit-breakers, four-pole, 100 A, 0,1 A, Type A, selective, N left

Type A residual current circuit-breakers detect pulsating direct current and alternating current. Selective circuit-breakers (S) are the ideal solution for systems with tiered distribution. In the event of a fault, only the downstream breaker in the affected section trips – ensuring targeted disconnection. Standard RCCBs are designed for circuits with 230/400 V at 50 Hz.

response delay for selective design, high immunity against surge currents and mains-voltage-operated secondary current impulses , tripping not dependent on mains and auxiliary voltage, sensitive to AC residual currents and pulsating DC residual currents (type A) , compact design for all rated currents, high short-circuit resistance, double-sided two-tier terminals for large conductor cross-section and busbar, switch position indicator, viewing window for labels, multifunction switch toggle with three positions: "on", "off" and "tripped", Neutral conductor position left

quick fastening to mounting rail, any installation position, supply from any direction

Main distribution boards in extended power supplies with TN-S, TT and TN-C-S systems, such as campsites, marinas, allotment gardens and showrooms. Selective residual current circuit-breakers in most cases protect the cables from the main distribution board to the sub-distribution boards, Excluded is the application in TN-C systems and for the protection of installations in which electronic equipment could generate smooth DC currents or residual currents with frequencies other than 50 Hz. Comprehensive protection is not provided in this case. For these applications we recommend our AC/DC sensitive residual current circuit-breakers (Type B or B+).

To ensure the selectivity of the RCCB, the rated residual current of the selective RCCB must be set at least one level higher than the downstream instantaneous switch.

Residual current circuit-breakers, four-pole, 100 A, 0,1 A, Type A, selective, N left

Type A residual current circuit-breakers detect pulsating direct current and alternating current. Selective circuit-breakers (S) are the ideal solution for systems with tiered distribution. In the event of a fault, only the downstream breaker in the affected section trips – ensuring targeted disconnection. Standard RCCBs are designed for circuits with 230/400 V at 50 Hz.

response delay for selective design, high immunity against surge currents and mains-voltage-operated secondary current impulses , tripping not dependent on mains and auxiliary voltage, sensitive to AC residual currents and pulsating DC residual currents (type A) , compact design for all rated currents, high short-circuit resistance, double-sided two-tier terminals for large conductor cross-section and busbar, switch position indicator, viewing window for labels, multifunction switch toggle with three positions: "on", "off" and "tripped", Neutral conductor position left

quick fastening to mounting rail, any installation position, supply from any direction

Main distribution boards in extended power supplies with TN-S, TT and TN-C-S systems, such as campsites, marinas, allotment gardens and showrooms. Selective residual current circuit-breakers in most cases protect the cables from the main distribution board to the sub-distribution boards, Excluded is the application in TN-C systems and for the protection of installations in which electronic equipment could generate smooth DC currents or residual currents with frequencies other than 50 Hz. Comprehensive protection is not provided in this case. For these applications we recommend our AC/DC sensitive residual current circuit-breakers (Type B or B+).

To ensure the selectivity of the RCCB, the rated residual current of the selective RCCB must be set at least one level higher than the downstream instantaneous switch.