00 81L 1111PPPPP90 000001 01 22.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12protect 000006 21000100001NNN 00000001000Pcs 000007 25Residual current operated 000008 25circuit-breaker with integral 000009 25overcurrent protection, one-pole+N, 20 000010 25A, 0.03 A, C-characteristic, Type AC 000011 26 Mains voltage independent RCCB with overcurrent 000012 26 protection (RCBO) for detection of AC residual 000013 26 currents (not admitted for use in Germany) 000014 26 suitable for retro-fitting of additional equipment 000015 26 000016 26 Tripping characteristic: C 000017 26 Residual current type: AC 000018 26 Rated residual current IΔn: 0.03 A 000019 26 Neutral conductor position: right 000020 26 Module widths: 2 000021 26 000022 26 load circuit (load disconnect contact): 000023 26 Number of poles: 2 000024 26 Rated voltage (AC): 230 V 000025 26 Rated current AC (typ.): 20 A 000026 26 Rated frequency: 50 Hz 000027 26 max. Total rated switching capacity: 10 kA 000028 26 Rated insulation voltage: 440 V 000029 26 000030 26 screw-type terminal top, bottom (load circuit): 000031 26 Cross section solid: 1-wire: 1 mmý ... 25 mmý 000032 26 Cross section stranded: 1-wire: 1 mmý ... 16 mmý 000033 26 Connecting capacity flexible: 1-wire: 1 mmý ... 16 mmý 000034 26 Ambient temperature: min. -25 øC ... max. 40 øC 000035 26 000036 26 Housing type: distribution board housing 000037 26 Installation type: Mounting rail (35 mm) 000038 26 Protection class: IP20 (installed: IP40) 000039 26 Dimensions of transformer opening: W 35 mm (2 MW 000040 26 (module width)) ž H 80 mm ž D 74 mm 000041 26 000042 26 Design requirements/Standards: EN 61009-1, EN 61009-2-1 000043 26 000044 26 Factory: Doepke or similar 000045 26 Item designation: DRCBO 3 C20/0,03/1N-AC 000046 26 Order number: 09933125 000047 26 selected make/type: ___________/___________ 000048 310001 000049 99 00001000050