00 81L 1111PPPPP90 000001 01 15.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12protect 000006 21000100001NNN 00000001000Pcs 000007 25Circuit-breakers, K-characteristic, 2 000008 25A/230 V, 400 V AC, 2 A/60 V DC, 10 kA, 000009 25for industrial facilities 000010 26 Miniature circuit-breakers (MCBs) of type DLS 6 are 000011 26 predominately used for overcurrent protection of 000012 26 cables and lines as per VDE 0100-430 and protection 000013 26 against electrical shock as per VDE 0100-410. 000014 26 Devices of the i design are fitted with a peculiar 000015 26 high rated switching capacity of 10 kA for industrial 000016 26 applications and provide screw terminals with top and 000017 26 bottom strain-relief clamps. 000018 26 special quick fastening for removal of multiple 000019 26 miniature circuit-breakers from the bottom or top 000020 26 interconnection 000021 26 large, folding label window for a secure hold and 000022 26 protection of the label 000023 26 use of conventional wiring rails 000024 26 ON/OFF switch position indicator on the switch toggle 000025 26 accessories retro-fittable on the right 000026 26 labelling software free of charge 000027 26 000028 26 Tripping characteristic: K 000029 26 Number of poles: 1 000030 26 Insulation group (250 V AC): C 000031 26 Isolation class (400 V AC): B 000032 26 000033 26 000034 26 load circuit (load disconnect contact): 000035 26 1 NO 000036 26 Number of poles: 1 000037 26 Rated voltage (AC): 230 V, 400 V 000038 26 Rated current AC (typ.): 2 A 000039 26 Rated frequency: 50 Hz (16.67 Hz ... 60 Hz) 000040 26 Rated voltage (DC): 60 V 000041 26 Rated current DC (typ.): 2 A 000042 26 Rated insulation voltage: 2 kV 000043 26 Rated switching capacity as of EN 60898 at 230 V: 10 kA 000044 26 000045 26 000046 26 screw terminals with strain-relief clamp top (load 000047 26 circuit): 000048 26 Cross section solid: 1-wire: 0.5 mmę ... 25 mmę 000049 26 Cross section stranded: 1-wire: 1.5 mmę ... 25 mmę 000050 26 Connecting capacity flexible: 1-wire: 1 mmę ... 16 mmę 000051 26 Cross section flexible with ferrule: 0.5 mmę ... 16 mmę 000052 26 000053 26 000054 26 screw terminals with strain-relief clamp bottom (load 000055 26 circuit): 000056 26 Cross section solid: 1-wire: 0.5 mmę ... 35 mmę 000057 26 Cross section stranded: 1-wire: 1.5 mmę ... 35 mmę 000058 26 Connecting capacity flexible: 1-wire: 1 mmę ... 25 mmę 000059 26 Cross section flexible with ferrule: 0.5 mmę ... 16 mmę 000060 26 000061 26 000062 26 000063 26 Ambient temperature: min. -25 űC ... max. 55 űC 000064 26 000065 26 000066 26 Housing type: distribution board housing 000067 26 Installation type: Mounting rail (35 mm) 000068 26 Protection class: IP20 000069 26 Dimensions of transformer opening: W 17.7 mm (1 MW 000070 26 (module width)) ž H 82.5 mm ž D 74 mm 000071 26 000072 26 000073 26 Design requirements/Standards: IEC 60947-2, DIN EN 000074 26 60947-2, VDE 0660-101 000075 26 000076 26 Factory: Doepke or similar 000077 26 Item designation: DLS 6i K02-1 000078 26 Order number: 09916553 000079 26 selected make/type: ___________/___________ 000080 310001 000081 99 00001000082