00 81L 1111PPPPP90 000001 01 22.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12protect 000006 21000100001NNN 00000001000Pcs 000007 25Circuit-breakers, B-characteristic, 16 000008 25A/230 V AC, 6 kA, for commercial sector 000009 25applications 000010 26 Miniature circuit-breakers (MCBs) of type DLS 6 are 000011 26 predominately used for overcurrent protection of 000012 26 cables and lines as per VDE 0100-430 and protection 000013 26 against electrical shock as per VDE 0100-410. 000014 26 Devices of the h design for workshops are fitted with 000015 26 a high rated switching capacity of 6 kA for 000016 26 residential applications and provide screw terminals 000017 26 with top and bottom strain-relief clamps. 000018 26 special quick fastening for removal of multiple 000019 26 miniature circuit-breakers from the bottom or top 000020 26 interconnection 000021 26 large, folding label window for a secure hold and 000022 26 protection of the label 000023 26 use of conventional wiring rails 000024 26 ON/OFF switch position indicator on the switch toggle 000025 26 accessories retro-fittable on the right 000026 26 labelling software free of charge 000027 26 000028 26 Tripping characteristic: B 000029 26 Number of poles: 1+N 000030 26 Insulation group (250 V AC): C 000031 26 000032 26 000033 26 load circuit (load disconnect contact): 000034 26 2 NO 000035 26 Number of poles: 2 000036 26 Rated voltage (AC): 230 V 000037 26 Rated current AC (typ.): 16 A 000038 26 Rated frequency: 50 Hz (16.67 Hz ... 60 Hz) 000039 26 Rated insulation voltage: 2 kV 000040 26 Rated switching capacity as of EN 60898 at 230 V: 6 kA 000041 26 000042 26 000043 26 screw terminals with strain-relief clamp top (load 000044 26 circuit): 000045 26 Cross section solid: 1-wire: 0.5 mmę ... 25 mmę 000046 26 Cross section stranded: 1-wire: 1.5 mmę ... 25 mmę 000047 26 Connecting capacity flexible: 1-wire: 1 mmę ... 16 mmę 000048 26 Cross section flexible with ferrule: 0.5 mmę ... 16 mmę 000049 26 000050 26 000051 26 screw terminals with strain-relief clamp bottom (load 000052 26 circuit): 000053 26 Cross section solid: 1-wire: 0.5 mmę ... 35 mmę 000054 26 Cross section stranded: 1-wire: 1.5 mmę ... 35 mmę 000055 26 Connecting capacity flexible: 1-wire: 1 mmę ... 25 mmę 000056 26 Cross section flexible with ferrule: 0.5 mmę ... 16 mmę 000057 26 000058 26 000059 26 000060 26 Ambient temperature: min. -25 űC ... max. 55 űC 000061 26 000062 26 000063 26 Housing type: distribution board housing 000064 26 Installation type: Mounting rail (35 mm) 000065 26 Protection class: IP20 000066 26 Dimensions of transformer opening: W 35.4 mm (2 MW 000067 26 (module width)) ž H 82.5 mm ž D 74 mm 000068 26 000069 26 000070 26 Design requirements/Standards: EN 60898-1 000071 26 000072 26 Factory: Doepke or similar 000073 26 Item designation: DLS 6h B16-1+N 000074 26 Order number: 09914053 000075 26 selected make/type: ___________/___________ 000076 310001 000077 99 00001000078