00 81L 1111PPPPP90 000001 01 22.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12switch 000006 21000100001NNN 00000001000Pcs 000007 25Mains field relays, 1 NO, 230 V AC, 16 000008 25A 000009 26 Mains field relay/mains disconnector to prevent 000010 26 electrical interference fields via automatic switch-off 000011 26 Switch-on threshold range power: 2 VA ... 15 VA 000012 26 Switch-on threshold range shading current: min. 0.009 000013 26 A ... max. 0.065 A 000014 26 Switch-on delay range: max. 8 s 000015 26 Switch-off delay range: max. 50 s 000016 26 000017 26 000018 26 load circuit (relays): 000019 26 1 NO 000020 26 Number of poles: 1 000021 26 Rated voltage (AC): 250 V 000022 26 Rated current AC (typ.): 16 A 000023 26 Rated frequency: 50 Hz, 60 Hz 000024 26 000025 26 max. Circuit cos phi = 0.6: 10 000026 26 max. Rated power glow lamps: 2300 VA 000027 26 max. Rated power fluorescent lamp compensated: 200 VA 000028 26 max. Rated power fluorescent lamp not compensated: 000029 26 1000 VA 000030 26 max. Rated power fluorescent lamps duo-switching: 1000 000031 26 VA 000032 26 000033 26 000034 26 Operating voltage (AC): 230 V (195.5 V ... 264.5 V) 000035 26 Operating frequency (fixed): 50 Hz, 60 Hz 000036 26 000037 26 000038 26 Housing type: distribution board housing 000039 26 Installation type: Mounting rail (35 mm) 000040 26 Protection class: IP30 000041 26 Dimensions of transformer opening: W 18 mm (1 MW 000042 26 (module width)) ž H 85 mm ž D 65 mm 000043 26 000044 26 Factory: Doepke or similar 000045 26 Item designation: FSE 1 000046 26 Order number: 09700108 000047 26 selected make/type: ___________/___________ 000048 310001 000049 99 00001000050