00 81L 1111PPPPP90 000001 01 22.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12protect 000006 21000100001NNN 00000001000Pcs 000007 25Residual current circuit-breakers, 000008 25four-pole, 40 A, 0.3 A, Type B SK, 000009 25Emergency shut-off function, N left 000010 26 000011 26 AC/DC sensitive residual current circuit-breakers 000012 26 (RCCBs) for detecting AC, pulsating and smooth DC 000013 26 residual currents 000014 26 sensitive to residual currents and mixed frequencies 000015 26 from 0 Hz to 150 kHz 000016 26 Integrated emergency shut-off device for tripping or 000017 26 disconnection in emergency situations with signalling 000018 26 by LED, wire breakage detection and the possibility of 000019 26 parallel switching of multiple DFS in NA design 000020 26 000021 26 doubled wiring level above and below 000022 26 switch position indicator and multifunction switch 000023 26 toggle with the functions "on", "off" and "tripped" 000024 26 (centre position) 000025 26 viewing window for labels 000026 26 000027 26 Residual current type: B 000028 26 Tripping characteristic curve: SK 000029 26 Rated residual current IΔn: 0.3 A 000030 26 000031 26 short-time delayed (lightning-resistant) 000032 26 Neutral conductor position: left 000033 26 Module widths: 4.5 000034 26 Number of poles: 4 000035 26 Rated voltage (AC): 230 V, 400 V 000036 26 Rated current AC (typ.): 40 A 000037 26 Rated frequency: 50 Hz 000038 26 000039 26 Auxiliary switch (additional emergency shut-off 000040 26 device) (switching contact): 000041 26 1 CO 000042 26 Rated voltage (AC): 12 V ... 230 V 000043 26 Rated voltage (DC): 12 V ... 110 V 000044 26 000045 26 screw-type terminal top and bottom (load circuit): 000046 26 Cross section solid: 1-wire: 1.5 mmę ... 50 mmę; 000047 26 2-wire: 1.5 mmę ... 16 mmę 000048 26 Cross section stranded: 1-wire: 1.5 mmę ... 50 mmę; 000049 26 2-wire: 1.5 mmę ... 16 mmę 000050 26 Connecting capacity flexible: 1-wire: 1.5 mmę ... 50 000051 26 mmę; 2-wire: 1.5 mmę ... 16 mmę 000052 26 Cross section AWG, solid: 15 ... 1 000053 26 Cross section AWG, stranded: 15 ... 1 000054 26 Cross section AWG, flexible: 15 ... 1 000055 26 Cross section AWG, flexible with ferrule: 15 ... 1 000056 26 000057 26 screw-type terminal top and bottom (Emergency shut-off 000058 26 device, auxiliary switches): 000059 26 Cross section solid: 1-wire: 1 mmę ... 1.5 mmę; 000060 26 2-wire: 1 mmę ... 1.5 mmę 000061 26 Cross section stranded: 1-wire: 1 mmę ... 1.5 mmę; 000062 26 2-wire: 1 mmę ... 1.5 mmę 000063 26 Cross section flexible with ferrule: 1 mmę ... 1.5 mmę 000064 26 Cross section AWG, solid: 17 ... 16 000065 26 Cross section AWG, stranded: 17 ... 16 000066 26 Cross section AWG, flexible with ferrule: 17 ... 16 000067 26 Ambient temperature: min. -25 űC ... max. 40 űC 000068 26 000069 26 Housing type: distribution board housing 000070 26 Installation type: Mounting rail (35 mm) 000071 26 Protection class: IP20 (installed: IP40) 000072 26 Dimensions of transformer opening: W 81 mm (4.5 MW 000073 26 (module width)) ž H 85 mm ž D 75 mm 000074 26 000075 26 Design requirements/Standards: VDE 0664-10, VDE 000076 26 0664-40, ™VE/™NORM E 8601, DIN EN 61008-1, EN 62423 000077 26 000078 26 Factory: Doepke or similar 000079 26 Item designation: DFS 4 040-4/0,30-B SK NA 000080 26 Order number: 09136861 000081 26 selected make/type: ___________/___________ 000082 310001 000083 99 00001000084