00 81L 1111PPPPP90 000001 01 22.03.24 000002 02 000003 08EUR 000004 110001 N 000005 12protect 000006 21000100001NNN 00000001000Pcs 000007 25Residual current circuit-breakers, 000008 25four-pole, 40 A, 0.03 A, Type A, with 000009 25emergency shut-off function, N right 000010 26 Mains voltage-independent residual current 000011 26 circuit-breaker (RCCB) for detecting AC residual 000012 26 currents and pulsating DC residual currents 000013 26 Integrated emergency shut-off device for tripping or 000014 26 disconnection in emergency situations with signalling 000015 26 by LED, wire breakage detection and the possibility of 000016 26 parallel switching of multiple DFS in NA design 000017 26 000018 26 doubled wiring level above and below 000019 26 switch position indicator and multifunction switch 000020 26 toggle with the functions "on", "off" and "tripped" 000021 26 (centre position) 000022 26 viewing window for labels 000023 26 000024 26 Residual current type: A 000025 26 Rated residual current IΔn: 0.03 A 000026 26 Neutral conductor position: right 000027 26 Module widths: 4.5 000028 26 Number of poles: 4 000029 26 Rated voltage (AC): 230 V, 400 V 000030 26 Rated current AC (typ.): 40 A 000031 26 Rated frequency: 50 Hz 000032 26 000033 26 Auxiliary switch (additional emergency shut-off 000034 26 device) (switching contact): 000035 26 1 CO 000036 26 Rated voltage (AC): 12 V ... 230 V 000037 26 Rated voltage (DC): 12 V ... 110 V 000038 26 000039 26 screw-type terminal top and bottom (load circuit): 000040 26 Cross section solid: 1-wire: 1.5 mmę ... 50 mmę; 000041 26 2-wire: 1.5 mmę ... 16 mmę 000042 26 Cross section stranded: 1-wire: 1.5 mmę ... 50 mmę; 000043 26 2-wire: 1.5 mmę ... 16 mmę 000044 26 Connecting capacity flexible: 1-wire: 1.5 mmę ... 50 000045 26 mmę; 2-wire: 1.5 mmę ... 16 mmę 000046 26 Cross section AWG, solid: 15 ... 1 000047 26 Cross section AWG, stranded: 15 ... 1 000048 26 Cross section AWG, flexible: 15 ... 1 000049 26 Cross section AWG, flexible with ferrule: 15 ... 1 000050 26 000051 26 screw-type terminal top and bottom (Emergency shut-off 000052 26 device, auxiliary switches): 000053 26 Cross section solid: 1-wire: 1 mmę ... 1.5 mmę; 000054 26 2-wire: 1 mmę ... 1.5 mmę 000055 26 Cross section stranded: 1-wire: 1 mmę ... 1.5 mmę; 000056 26 2-wire: 1 mmę ... 1.5 mmę 000057 26 Cross section flexible with ferrule: 1 mmę ... 1.5 mmę 000058 26 Cross section AWG, solid: 17 ... 16 000059 26 Cross section AWG, stranded: 17 ... 16 000060 26 Cross section AWG, flexible with ferrule: 17 ... 16 000061 26 Ambient temperature: min. -25 űC ... max. 40 űC 000062 26 000063 26 Housing type: distribution board housing 000064 26 Installation type: Mounting rail (35 mm) 000065 26 Protection class: IP20 (installed: IP40) 000066 26 Dimensions of transformer opening: W 81 mm (4.5 MW 000067 26 (module width)) ž H 85 mm ž D 75 mm 000068 26 000069 26 Design requirements/Standards: VDE 0664-10, VDE V 000070 26 0664-120, DIN EN 61008-1 000071 26 000072 26 Factory: Doepke or similar 000073 26 Item designation: DFS 4 040-4/0,03-A NA R 000074 26 Order number: 09134842 000075 26 selected make/type: ___________/___________ 000076 310001 000077 99 00001000078